MRI suite with the RF shielded door open
RF shielded doors

MRI RF Door Supplier in China for Shielded Scan Rooms

YK Door is an MRI RF door supplier in China, building swing and power-operated sliding RF shielded doors for MRI examination rooms. Our doors are tested to IEEE 299, with conductive seals and finger stock that keep the contact line continuous, and interface details agreed with the RF room integrator.

Tested to IEEE 299swing or power-operated slidingreplaceable conductive sealsintegrator coordination
02 / Overview

The door is the most-used part of the RF room

An MRI room's walls, floor and ceiling form a sealed RF enclosure. The door is the one part that opens many times a day, so it is where shielding is most likely to drift. Our design keeps the conductive contact even and repeatable: a stiff leaf, precise hinges or tracks, and seals that can be replaced without changing the frame.

Product views

MRI RF doors from every angle

Six views of one mri rf door set: the face, the hinge side, the open leaf, the hardware, the section and the door in service. Open any view full screen to see the detail.

1 / 6
MRI suite with the RF shielded door open
MRI RF shielded door seen from the hinge side
MRI RF shielded door shown open
Close-up of the MRI RF shielded door lever handle and lock
Cut-away section of a MRI RF shielded door showing the leaf core and frame
MRI RF shielded door installed in a hospital corridor
Models and sizes

Models, configurations and sizes

Each model ties to its own test or certification route, so the door you order is the door that was tested.

ModelConfigurationPerformanceStandard
YK-RF60Single, heavy-duty floor pivot; sets per project100 dB or more from 100 MHz to 1 GHzIEEE 299

Sizes and build

Clear opening
1100–1500 × 2100–2400 mm
Largest covered size
Single 1200 × 2400 mm; larger openings built per project
Leaf thickness
50–70 mm
Materials and finish
Steel faces, copper shielding layer, mineral core, beryllium copper finger stock, non-magnetic hardware
Other sizes

Built to your opening size. Send the clear opening and wall type, and we confirm the leaf, frame and hardware with drawings.

Single swingDouble swingAutomatic slidingPersonnel opening, single leafWide opening, double leaf or bi-parting

Related products

Compare in the product finder

03 / Comparison

Swing or sliding

RF swing door

Best forStandard scan rooms, compact layouts
ContactFinger stock or conductive gasket around the frame
OperationManual, with heavy-duty hinges and closing aid
Clear openingSingle or double leaf
MaintenanceSeal strips replaced by door ID

Power-operated RF sliding door

Best forWide patient openings, busy departments
ContactConductive seals pressed into contact as the leaf closes
OperationPowered, with safety sensors on the leaf edge
Clear openingSingle or bi-parting
MaintenanceSeal strips and drive serviced by door ID
04 / Step by step

Where RF shielding fails

1

Leaf sag

Opens a gap in the contact line.

2

Oxidized or dirty contact faces

Raise resistance.

3

Worn conductive gaskets

Lose pressure.

4

Holes cut on site

After installation.

We design against all four, and set out in writing where factory testing ends and on-site room testing begins.

05 / Overview

RF door and magnetic shielding

RF shielding and static magnetic shielding are different technologies. We supply the RF door, its shielded vision panel and its interface details. Magnetic shielding, where the room needs it, is delivered by the specialist shielding integrator, and we coordinate the door interface with them. The attenuation figures and test method are set by the project, typically measured point by point across the frequency bands, and confirmed with the integrator.

Copper finger stock on the edge of an MRI RF shielded door
06 / Key points

What ships with the door

  • Door leaf, frame and conductive seals or finger stock
  • Shielded vision panel and frame where needed. See components.
  • Interface details for the RF enclosure
  • Commissioning instructions and a contact-face maintenance schedule
  • Spare seal strips packed by door ID
  • FAT records, and SAT support for room testing
07 / Overview

Where our MRI doors go

Hospital MRI suites, outpatient imaging centers and research MRI facilities. MRI doors often ship with X-ray and CT room doors in one imaging department package, each with its own door ID. See doors for healthcare.

Evidence

Certificates and test reports for MRI RF doors

The documents behind the claims on this page, at the model and configuration that were assessed. Copies go with the submittal for your project.

IEEE 299 RF shielding effectiveness test report for YK Door MRI RF shielded doors
IEEE 299 · RF shielding effectiveness, MRI RF doorsets
FAQ

MRI RF doors: questions buyers ask

We supply the RF door and its interface details, and work with the RF room integrator who builds the enclosure.

09 / Item

Key MRI RF door specifications

ItemSpecification
ConfigurationsSwing (single or double), power-operated sliding (single or bi-parting)
Design standardTested to IEEE 299
ContactConductive gaskets or finger stock, replaceable
LeafStiff construction to prevent sag
Hinges and tracksPrecision hardware to keep contact even
Vision panelShielded window with conductive mesh and frame
InterfaceDetails agreed with the RF room integrator
DocumentsInterface details, commissioning instructions, maintenance schedule

Evidence cards

YK-RF60

IEEE 299 tested MRI RF door

Evidence
Tested to IEEE 299
Number
NIM-2025-RF-0118
Result
100 dB or more from 100 MHz to 1 GHz
Size range
Single leaf to 1600×2400 mm
Construction
Copper mesh shield; finger stock in the frame; waveguide vent; filtered interfaces

Numbers are given as issued. See the full certificate register.

10 / Term

MRI RF doors: terms that get mixed up

01RF shielding

Keeps radio frequency interference out of the scan room

02Magnetic shielding

Controls the static magnetic field; a different technology

03Attenuation

How much the room reduces RF signal, measured across frequencies

04Finger stock

Spring contacts that make the conductive seal at the door edge

11 / Step by step

Specification clauses for MRI RF doors

1

Standard

RF doors shall be tested to IEEE 299, with attenuation and test method as set by the project.

2

Contact

Conductive seals or finger stock shall be replaceable without removing the frame.

3

Interface

Door-to-enclosure interface details shall be agreed with the RF room integrator.

4

Vision panel

Where shown, a shielded window matched to the room's attenuation.

5

Testing

Factory and room test responsibilities shall be stated in writing.

12 / Condition

Door states for powered doors

Condition

Normal

What must be defined
Opening and closing, status feedback
13 / Stage

From delivery to acceptance: MRI RF doors

Stage

Enclosure

What is checked
Integrator's frame interface ready
14 / Key points

Keeping MRI RF doors in service

  • Inspect contact faces and finger stock on the schedule we supply.
  • Clean contact faces only with the method in the schedule.
  • Replace worn strips by door ID; spares ship with every door.
  • Never drill the leaf or frame after installation.
Request a quote

Send your RF room drawings

Send the room drawings, attenuation figures, frequency range and opening sizes, and an engineer will reply with a configuration. MRI doors are part of our RF shielded door range. Learn more about YK Door, a China specialty door manufacturer.

1An engineer reviews each opening against its wall, standard and market.
2You receive a priced configuration per opening, or the questions that stand in the way.
3On approval, we send the English submittal with drawings, data sheets and an evidence index.

Ask for a specification review

Your files stay with our engineering team and are used only to prepare your quotation.

Scroll to Top