Browse all articlesIEC 61331-1 sets how the attenuation of protective materials against diagnostic X-rays is measured and stated as a lead equivalent. YK Door's X-ray shielding doors are tested to IEC 61331-1 at the National Institute of Metrology, China (report NIM-2024-RS-0271): the YK-R20 at 2.0 mmPb at 120 kV and the YK-R30 at 3.0 mmPb at 150 kV.
A door's lead equivalent is the thickness of pure lead that gives the same attenuation as the door, at a stated tube voltage. That is why the voltage always travels with the number: 2.0 mmPb at 120 kV is a different claim from 2.0 mmPb at 150 kV. IEC 61331-1 fixes how that measurement is made, so figures from different suppliers can be compared.
| Model | Evidence | Number | Result | Size |
|---|---|---|---|---|
| YK-R20 | Tested to IEC 61331-1 | NIM-2024-RS-0271 | 2.0 mmPb at 120 kV | Single leaf to 1500×2400 mm; pair to 3000×2400 mm |
| YK-R30 | Tested to IEC 61331-1 | NIM-2024-RS-0271 | 3.0 mmPb at 150 kV | Single leaf to 1500×2400 mm; pair to 3000×2400 mm |
Tested at the National Institute of Metrology, China, on a whole door specimen with the leaf overlap included. Lead glass vision panels go up to 800×1000 mm. See the full certificate register.
The documents behind the claims on this page, at the model and configuration that were assessed. Copies go with the submittal for your project.

The shielding requirement comes from the project's physicist, who works it out from workload, use and occupancy, often following NCRP Report 147 or IAEA SSG-46. The report states the lead equivalent each wall and door needs. We match the door to that figure and keep the shielding continuous at the frame, the leaf edges, the lock and the vision panel.
See CT room doors for rooms with heavy daily use. The floor line is covered in detail in our guide to radiation shielded door thresholds and X-ray room door shielding requirements.
Imaging doors often need to be automatic, hermetic, fire-rated or quiet as well as shielded. We build lead-lined doors with automatic sliding drives, airtight seals for clean areas and acoustic seals, and check each added duty against the shielding build. See doors for hospitals and the full radiation shielding door range.
The figure from the shielding report, with its tube voltage.
Lead equivalence tested to IEC 61331-1.
Shielding continuous through frame, edges, hardware and glazing.
Manual or automatic, swing or sliding, with safety sensors.
Fire, airtightness or acoustic needs per opening.
Interlock with the X-ray warning light where required.
Our YK-R20 is tested to IEC 61331-1 at 2.0 mmPb at 120 kV, and our YK-R30 at 3.0 mmPb at 150 kV.
The project's radiation physicist, through the shielding report. We build the door to the figure in that report.
Yes. We supply automatic sliding and swing lead-lined doors with safety sensors and interlocks.
Yes. Vision panels use lead glass rated to the same lead equivalent, in a lead-lined frame.
Send the shielding report and door schedule, and an engineer will reply with a configuration per opening. See our X-ray shielding doors, the full radiation shielding door range, all standards we work to, or learn more about YK Door as a China specialty door manufacturer.