EN 1634-3 Smoke Control Doors from a China Manufacturer

A smoke control door keeps cold and hot smoke on the fire side long enough for people to leave and for the smoke system to work. In Europe the leakage is tested to EN 1634-3 and classified as Sa or S200, and EN 15269-20 extends that result to other sizes and hardware. In North America the same job is done by UL 1784 and the S label. Our YK-S90-S steel smoke control door is tested to EN 1634-3 at Sa and S200, extended under EN 15269-20 and UL 1784 listed.

STANDARDYK DOOR · EVIDENCE INDEX
EN 1634-3 Smoke Control
§1EN 1634-3 Sa / S200
§2EN 15269-20
§3UL 1784 S label
§4single leaf to 1200×2400 mm
§5pair to 2400×2400 mm
Tested
02 / Overview

Fire resistance and smoke leakage are two results

A fire door rating tells you how long the door holds back flames and heat. A smoke rating tells you how much smoke passes the door gaps. They come from different tests on different specimens, so a door carries two results side by side, such as EI2 60-C5 Sa. Smoke moves first and travels furthest, so in corridors, lobbies and stair cores the smoke figure often decides the door.

03 / Model

Our evidence

ModelEvidenceNumberResultSize
YK-S90-STested to EN 1634-3WF 415026/BSa and S200Single leaf to 1200×2400 mm
YK-S90-SExtended under EN 15269-20ift 23-003112-PR01Sa and S200 extended across the Annex 3 rangeSingle leaf to 1200×2400 mm; pair to 2400×2400 mm
YK-S90-SUL 1784 listed, S labelUL file E1753 · FD-10C-01-S; test report UL-CN-25-118402-TR01Leakage within limits at 0.10, 0.20 and 0.30 in. w.g.Single leaf 600×1800 to 1200×2400 mm; pair to 2400×2400 mm
YK-S60-CECE marked under EN 16034DoP YK-EN16034-2023-014EI2 60-C5 SaSingle leaf 600×1800 to 1200×2400 mm

The extended application assessment was issued by ift Rosenheim, Notified Body 0757. The tested build is a 1.5 mm galvanized steel leaf with a rock wool core, perimeter intumescent seals with cold smoke seals, an automatic drop seal at the threshold and a steel frame.

04 / Class

Reading Sa and S200

ClassTest conditionWhat it tells you
SaAmbient temperature, up to 25 PaCold smoke held back in the early stage of a fire
S200Ambient and 200 °C, up to 50 PaHot smoke held back as the fire grows
S label (UL 1784)Ambient and 400 °F, at 0.10 in. w.g. and aboveThe North American route for smoke and draft control doors

Sa and S200 are written after the fire class under EN 13501-2, for example EI2 60-C5 Sa.

05 / Overview

What EN 15269-20 adds

A smoke test is run on one specimen of one size with one set of hardware. Real projects need other sizes, pairs, vision panels and different locks. EN 15269-20 is the European rule set for extending a smoke control result to those variations without a new test. Our assessment, ift 23-003112-PR01, extends Sa and S200 for the YK-S90-S to single leaves up to 1200×2400 mm and pairs up to 2400×2400 mm, with the hardware and seal substitutions listed in its Annex 3.

For the fire resistance of the same door, the size range is extended under EN 15269-2 (ift 23-001977-PR02). The two assessments sit side by side in our submittal, one for smoke and one for fire. See EN 16034 and EN 1634 fire doors.

Steel fire door with panic bar and closer in a stair core
06 / Overview

Where smoke doors go

Stair lobbies, corridor cross-walls, lift lobbies, firefighting shafts and the doors between a car park and the building core. Hospitals use them on ward corridors, so patients can stay behind a smoke barrier while staff move them. See our steel fire doors and hospital doors.

07 / Part

What keeps a door inside its smoke class

Part

Perimeter seals

What we hold to the assessment
Intumescent seal plus cold smoke seal, in the tested positions

Each door carries its own ID, so the build on site can be traced to the configuration in the assessment.

FAQ

En 1634 3 smoke control doors: questions buyers ask

Yes. Our YK-S90-S is tested to EN 1634-3 at Sa and S200, report WF 415026/B.

09 / Step by step

How to specify smoke control doors

01

Classes

Fire class and smoke class per opening, for example EI2 60-C5 Sa or EI2 60 S200.

02

Evidence

Test to EN 1634-3, extended application under EN 15269-20, classification to EN 13501-2.

03

Size and type

Single or pair, clear opening and swing.

04

Seals

Perimeter, meeting stile and threshold seals as assessed.

05

Hardware

Selected from the assessed range, with door closers on every leaf.

06

North America

UL 1784 listed, S label, where the code calls for smoke and draft control.

Request a quote

Send your smoke door schedule

Send the door schedule with fire and smoke classes per opening, and an engineer will reply with configurations inside the tested and assessed range. See our steel fire doors, fire rated doors, UL 10B and UL 10C fire doors, all standards we work to, or our certificate register.

1An engineer reviews each opening against its wall, standard and market.
2You receive a priced configuration per opening, or the questions that stand in the way.
3On approval, we send the English submittal with drawings, data sheets and an evidence index.