Browse all articlesA smoke control door keeps cold and hot smoke on the fire side long enough for people to leave and for the smoke system to work. In Europe the leakage is tested to EN 1634-3 and classified as Sa or S200, and EN 15269-20 extends that result to other sizes and hardware. In North America the same job is done by UL 1784 and the S label. Our YK-S90-S steel smoke control door is tested to EN 1634-3 at Sa and S200, extended under EN 15269-20 and UL 1784 listed.
A fire door rating tells you how long the door holds back flames and heat. A smoke rating tells you how much smoke passes the door gaps. They come from different tests on different specimens, so a door carries two results side by side, such as EI2 60-C5 Sa. Smoke moves first and travels furthest, so in corridors, lobbies and stair cores the smoke figure often decides the door.
| Model | Evidence | Number | Result | Size |
|---|---|---|---|---|
| YK-S90-S | Tested to EN 1634-3 | WF 415026/B | Sa and S200 | Single leaf to 1200×2400 mm |
| YK-S90-S | Extended under EN 15269-20 | ift 23-003112-PR01 | Sa and S200 extended across the Annex 3 range | Single leaf to 1200×2400 mm; pair to 2400×2400 mm |
| YK-S90-S | UL 1784 listed, S label | UL file E1753 · FD-10C-01-S; test report UL-CN-25-118402-TR01 | Leakage within limits at 0.10, 0.20 and 0.30 in. w.g. | Single leaf 600×1800 to 1200×2400 mm; pair to 2400×2400 mm |
| YK-S60-CE | CE marked under EN 16034 | DoP YK-EN16034-2023-014 | EI2 60-C5 Sa | Single leaf 600×1800 to 1200×2400 mm |
The extended application assessment was issued by ift Rosenheim, Notified Body 0757. The tested build is a 1.5 mm galvanized steel leaf with a rock wool core, perimeter intumescent seals with cold smoke seals, an automatic drop seal at the threshold and a steel frame.
| Class | Test condition | What it tells you |
|---|---|---|
| Sa | Ambient temperature, up to 25 Pa | Cold smoke held back in the early stage of a fire |
| S200 | Ambient and 200 °C, up to 50 Pa | Hot smoke held back as the fire grows |
| S label (UL 1784) | Ambient and 400 °F, at 0.10 in. w.g. and above | The North American route for smoke and draft control doors |
Sa and S200 are written after the fire class under EN 13501-2, for example EI2 60-C5 Sa.
A smoke test is run on one specimen of one size with one set of hardware. Real projects need other sizes, pairs, vision panels and different locks. EN 15269-20 is the European rule set for extending a smoke control result to those variations without a new test. Our assessment, ift 23-003112-PR01, extends Sa and S200 for the YK-S90-S to single leaves up to 1200×2400 mm and pairs up to 2400×2400 mm, with the hardware and seal substitutions listed in its Annex 3.
For the fire resistance of the same door, the size range is extended under EN 15269-2 (ift 23-001977-PR02). The two assessments sit side by side in our submittal, one for smoke and one for fire. See EN 16034 and EN 1634 fire doors.

Stair lobbies, corridor cross-walls, lift lobbies, firefighting shafts and the doors between a car park and the building core. Hospitals use them on ward corridors, so patients can stay behind a smoke barrier while staff move them. See our steel fire doors and hospital doors.
Each door carries its own ID, so the build on site can be traced to the configuration in the assessment.
Yes. Our YK-S90-S is tested to EN 1634-3 at Sa and S200, report WF 415026/B.
The extended application of a smoke control result: sizes, pairs, hardware and seals beyond the tested specimen. Ours is ift 23-003112-PR01.
The fire rating is extended under EN 15269-2. We hold both assessments for the same door family.
Yes. The YK-S90-S is UL 1784 listed with the S label, UL file E1753, listing FD-10C-01-S.
Fire class and smoke class per opening, for example EI2 60-C5 Sa or EI2 60 S200.
Test to EN 1634-3, extended application under EN 15269-20, classification to EN 13501-2.
Single or pair, clear opening and swing.
Perimeter, meeting stile and threshold seals as assessed.
Selected from the assessed range, with door closers on every leaf.
UL 1784 listed, S label, where the code calls for smoke and draft control.
Send the door schedule with fire and smoke classes per opening, and an engineer will reply with configurations inside the tested and assessed range. See our steel fire doors, fire rated doors, UL 10B and UL 10C fire doors, all standards we work to, or our certificate register.