Browse all articlesIEEE 299 is the standard method for measuring the shielding effectiveness of shielded enclosures, from MRI rooms to EMC test chambers. The door is the hardest part of the enclosure to keep tight, because it opens many times a day. Our YK-RF60 MRI RF door is tested to IEEE 299 at 100 dB or more from 100 MHz to 1 GHz, report NIM-2025-RF-0118.
IEEE 299 places a transmitting antenna on one side of the shield and a receiving antenna on the other, then compares the signal with and without the shield in the path. The difference, in decibels, is the shielding effectiveness. Every 20 dB is a tenfold drop in field strength, so 100 dB means the field outside is one hundred thousandth of the field inside. Measurements are taken around the door seams, where leaks start.
| Model | Evidence | Number | Result | Size |
|---|---|---|---|---|
| YK-RF60 | Tested to IEEE 299 | NIM-2025-RF-0118 | 100 dB or more, 100 MHz to 1 GHz | Single leaf to 1600×2400 mm |
The tested door uses a copper mesh shield inside the leaf, finger stock along the frame, a waveguide vent and filtered interfaces. We also keep site acceptance records from finished MRI rooms.
Continuous finger stock, replaceable in sections
Copper mesh lapped and bonded at every joint
Kept outside the contact line
Mesh glass bonded to the frame
Contact strip that survives traffic and cleaning
Bonded to the integrator's shield panels
A shielding figure belongs to the whole room, not the door alone. The MRI vendor sets the attenuation and frequency range, the room integrator builds the shield, and our door is bonded into it. We agree the frame detail with the integrator before production, so the contact line meets the room shield without a gap. After installation, the integrator tests the finished room to the vendor's figures. See our RF shielded door range.

Finger stock wears. Over thousands of cycles, fingers bend, collect dirt or lose contact. Our finger stock is fixed in short sections that can be replaced on site without removing the door. We recommend an inspection of the contact line at each service visit and a room test whenever sections are replaced.
RF doors tested to IEEE 299, with attenuation and frequency range from the MRI vendor or room specification.
Swing or power-operated sliding, with clear opening per room.
Replaceable finger stock or conductive gaskets along the full perimeter.
Vision panel, waveguide vents and filtered cable entries as needed.
Frame bonding agreed with the shield integrator.
IEEE 299 report, drawings and a room test after installation.
Yes. Our YK-RF60 is tested to IEEE 299 at 100 dB or more from 100 MHz to 1 GHz, report NIM-2025-RF-0118.
The MRI vendor's site planning guide. The room integrator builds to it, and our door is matched to it.
Yes. It is fixed in short sections, replaceable without taking the door off.
Yes. We build large sliding and swing RF doors for EMC test chambers and shielded rooms to the project's figures.
Send the room drawings and the attenuation figures, and an engineer will reply with a door configuration and frame detail. See our MRI RF doors, the RF shielded door range, radiation shielding to IEC 61331-1, all standards we work to, or our certificate register.
Your files stay with our engineering team and are used only to prepare your quotation.