Single leaf 90 minutes, double leaf 60 minutes, also CE marked and Certifire certified for export projects.
See fire-rated doorsAll products, with filters
X-ray, CT, MRI RF, airtight theater and fire doors on one submittal set, one ID per door.
See healthcare doors
How to read what a certificate, listing or test report actually proves.
Read the guide
Engineering guides on sourcing, test evidence and every specialty door type, written by YK engineers.
Browse all articlesWind load fire doors hold a fire compartment on an external opening, where the leaf also takes wind pressure and rain. YK Door builds FD30 and FD60 steel and timber doors tested to EN 1634-1 for the fire duty and engineered to the project design wind pressure, with the frame and anchors sized for both.



An internal fire door is judged on one face and one set of gaps. An external one is pushed and pulled by wind, rained on, and expected to keep the same gap after years of pressure cycles. We size the frame and anchors to the design wind pressure, so the gap the fire test measured is the gap the door keeps.
Six views of one wind-load fire door set: the face, the hinge side, the open leaf, the hardware, the section and the door in service. Open any view full screen to see the detail.






Each model ties to its own test or certification route, so the door you order is the door that was tested.
| Model | Configuration | Performance | Standard |
|---|---|---|---|
| YK-S90 | Single, double, unequal pair (wind-load build) | Fire 30 or 60 min; wind pressure calculated per project | Tested to ASTM E330 at 3.5 kPa (73 psf) |
Sizes and build
Built to your opening size. Send the clear opening and wall type, and we confirm the leaf, frame and hardware with drawings.
Related products
| Duty | Test or design route | What we issue |
|---|---|---|
| Fire resistance | Tested to EN 1634-1, classified to EN 13501-2; UL 10B/10C where specified | FD30 and FD60 builds on their own reports; FD90 on YK-S90 at EI2 90 |
| Wind load | Design pressure to EN 1991-1-4, or ASTM E330 where a US specification names it | Calculation, deflection check and anchor reactions with the drawing set |
| Deflection | Limit stated by the project, commonly span/200 | Deflection check per opening |
| Weather | Drained sill, weep path and stainless threshold pan | Sill detail on the shop drawing |
| Finish | Coating system to the exposure category | Dry-film readings issued with the batch |
The fire report and the wind calculation travel as two documents, and the submittal names which one covers which claim. For internal compartment doors, see our steel fire doors.
The documents behind the claims on this page, at the model and configuration that were assessed. Copies go with the submittal for your project.

Wind pressure acts on the leaf area and travels through the hinges, the frame and the anchors into the wall. A 1 kPa design pressure on a 1.2 × 2.4 m (47 × 94 in.) opening puts about 2.9 kN on the leaf, and that load reaches the structure through the anchors.
We ask for the wall build-up, the concrete or block strength and the fixing detail at RFQ stage. We specify chemical anchors into grouted cores or a continuous steel sub-frame at the hinge side, and we issue the anchor reactions so the wall engineer can check the embedment in the same drawing cycle.
Rain is the third duty. The threshold drains, the sill sheds water away from the frame, and the raised sill is drawn as part of the fire detail because it sets the undercut and the drop seal.
The design pressure is the same number the facade engineer uses for the cladding. We take it from the project, size the frame, anchors and hinge reinforcement to it, and issue the calculation and anchor reactions with the drawings, so the door and the wall are checked against one load.
It comes from the local code, the building height and the exposure at that facade, and it is the same number the facade engineer uses for the cladding. Send the pressure and the opening size, and we size the frame, anchors and hinge reinforcement to it.
The fire rating covers a leaf thickness, a frame section and a hardware set. We keep the leaf inside the tested build and carry the wind load in the frame and anchors, where the fire test covered that section.
Chemical anchors into grouted cores or a continuous steel sub-frame at the hinge side, at 400 to 600 mm (16 to 24 in.) centers, with the pattern and embedment issued as anchor reactions.
With a drained sill, a weep path and a stainless threshold pan, so the frame pocket drains. The threshold is drawn as part of the fire detail, and we check the drain on the shop drawing.
Yes, on sheltered or semi-exposed openings, with a drained sill and a protected head. For a fully exposed facade we recommend a steel leaf and say so in the quotation.
The fire rating, the design wind pressure and exposure category, the wall section at the opening, the sill detail, the finished floor level and any deflection limit from the facade engineer.
Numbers are given as issued. See the full certificate register.
How long the whole doorset holds back fire, tested to EN 1634-1 or UL 10B/10C
The positive and negative pressure the opening must carry, from the local code
How far the leaf and frame may bow under that pressure, commonly span/200
The load each fixing passes into the wall, issued for the wall engineer
A fire report describes fire performance and a wind calculation describes the structural duty. We issue both, per opening, and state which document supports which line of the schedule.
Sample clauses for architects and facade engineers:
Doorsets shall carry the fire rating on the schedule, tested to EN 1634-1 or UL 10B/10C as the complete assembly supplied.
Doorsets shall resist the design wind pressure stated for each opening, with the calculation issued with the shop drawings.
Leaf and frame deflection shall not exceed the stated limit, span/200 unless noted.
Anchor type, spacing and reactions shall be issued per opening for review by the wall engineer.
The sill shall drain through a weep path, with a stainless threshold pan.
The coating system shall suit the exposure category, with dry-film readings issued per batch.
Send the fire rating, the design wind pressure, the wall section and the sill detail, and an engineer will return the tested build, the anchor pattern, the deflection check and a written lead time. Wind-load rated fire doors are part of our fire-rated door range, alongside fire-rated acoustic doors for openings with a sound target. Read the EN 16034 and EN 1634-1 guide for the classification route.